ECP 200 EXPERT D7.5
Brochure download

CONTROL PANEL FOR COLD ROOMS

Control panel for cold rooms with single-phase compressor up to 2  HP and single-phase or three-phase electrical defrosting up to 7500W, specially designed to provide safety, protection, control and easy-installation – all  in one unit. It allows a complete control of all the components on  a refrigeration system or the control of units only.

 

Applications
Complete control of single-phase static or ventilated refrigeration systems up to 2 HP, with off-cycle or electrical defrosting up to 7500W and direct or pump-down compressor stop.
Management of single-phase evaporating unit alone with electric defrosting up to 7,500W and with Freon solenoid consent or remote motor condensation unit consent .

Main characteristics
Direct control of compressor, defrosting heaters, evaporator fans and room light with live outputs directly connectable to the various devices or free voltage contacts for control of condensing unit   with its own electrical panel.
Innovative, stylish design. Transparent cover for access to magnetothermic breaker, all with  IP 65 protection rating.
Auxiliary relay with parameter-configured  activation (alarm, temperature set-point, direct  control via frontal pushbutton, door heater  elements, remote motor condenser unit  enabling, freon solenoid control enabling where  compressor pump-down operation is applied).
RS485 for connection to TeleNET industrial  supervision network or Modbus-RTU standard  protocol.
Easy installation and opening thanks to new  hinged cove.
Electrical defrosting up to 7500W.
Possibility of using defrosting contactor control fans or light.

 

TECHNICAL CHARACTERISTICS
ECP 200 EXPERT D7.5
Dimension
262 x 168 x 97 mm
Weight 0,6 Kg
POWER SUPPLY
Voltage 230 VAC ±10% 50/60 Hz
400 VAC 3/N ±10% 50/60 Hz
Max absorbed power
7 VA

AMBIENT CONDITIONS
Working temperature
-5 ÷ +50°C
Storage temperature -30 ÷ +70°C
Relative ambient humidity
<90% Rh
GENERAL CHARACTERISTICS
Connectable sensor types
NTC 10 KΩ
Resolution 0,1 °C
Probe read precision
± 0,5 °C
Read range
-45 ÷ +45°C
OUTPUTS CHARACTERISTICS
Compressor 1500 W (2HP)
Defrost 7500 W (2500 W x 3) (*)
(*) = 3000 W if the contactor is used for other functions
Fans 500 W (AC3) (**)
(**) =
For this output the defrosting contactor can be used to increase power
Room light
800 W (AC1) (**)
(**) =
For this output the defrosting contactor can be used to increase power
Configurable alarm contact / AUX PRESENT
Supervision system TELENET/MODBUS-RTU
INSULATION AND MECHANICAL CHARACTERISTICS
Box protection rating IP 65
Box material Self-extinguishing ABS
Insulation type Class II
DIMENSION
ECP200-EXPERT-D7.5
CONNECTION SCHEME
ECP200-EXPERT-D7.5

(*) = Configurable function

 