Man in cold room alarm kit: consisting of control unit with acoustic / visual warning, comes complete with buffer battery and luminous emergency in-room pushbutton. The kit allows a person trapped inside the cold room to activate an acoustic-luminous alarm installed outside the room and so call for help. The system will work even in the event of a temporary power cut thanks to the buffer battery on the external unit.
|
|


|
|
|
|
Applications • “Man in room” safety system for low-temperature rooms.
Main characteristics • Emergency pushbutton to be fitted inside cold room. This is a luminous mushroom-shaped pushbutton with a N.C. contact. The pushbutton is illuminated by LEDs, thus making it easy to find even in the dark. • Acoustic-visual alarm control unit to be fitted outside the room. Features a siren and a flashing light and a buffer battery to provide power in the event of a black-out. Also has a clean contact (closed when alarm is active) that can be used to inhibit refrigeration, switch on the interior room light or activate other devices such as a dialer for remote alarm activation.
|
|
TECHNICAL CHARACTERISTICS
|
|
ECP APE 03
|
|
| Dimension |
|
Control unit: 203x193x79 mm Pushbutton: 68x68x53 mm
|
|
| Weight |
|
2 Kg |
|
Main power supply
|
|
230 V AC 50 Hz
|
|
Max consuption on main power supply
|
|
20 mA
|
|
Buffer battery
|
|
12 VD C Ni-MH 1300 mAh Complete recharge time : 110 h |
|
Autonomy
|
|
• With 230 V AC power off (operation with charged buffer battery: about 14h) • With 230 V AC power on: unlimited |
|
External module
|
|
IP 43 protection rating
|
|
Working temperature
|
|
-5 ÷ +45°C
|
|
Acoustic characteristics |
|
Type: piezoelectric Sound power: 95 dB at 1m |
|
Visual warning
|
|
Red flashing led 12 VDC
|
|
In-room emergency pushbutton
|
|
In-room emergency pushbutton red flashing LED 12 Vdc NC contact Keyboard with IP 65 protection rating Operating temperature : -25 ÷ +70 °C |
|
|
|
Auxiliary relay
|
|
8A AC1 (contact closes when alarm is switched on)
|
|
| DIMENSION |
|
|
|
|
 |
|
CONNECTION SCHEME
|
|
|
|
|
 |
|
|
|
control unit to be fitted outside the room. Features a siren and a flashing light and a buffer battery to provide power in the event of a black-out. Also has a clean contact (closed when alarm is active) that can be used to inhibit refrigeration, switch on the interior room light or activate other devices such as a dialer for remote alarm activation