ECP400/750/1000 BASE4 VD
Brochure download

LINE OF CONTROL PANELS FOR COLD ROOM

A line of control panels for cold rooms with three-phase compressor up to 10 HP, specially designed  for complete cold room management.
Together with the various options, the different power  ranges allow the user to select a unit that is “custom- made” to suit the refrigeration system.

Applications
Complete control of three-phase static or ventilated refrigeration systems up to 10 HP, off-cycle or electrical defrosting.

Options
Installation of magnetothermic protection  devices instead of fuses.
Alarm output with free-voltage contact to activate further warning devices such as siren or dialer.
Pump-down compressor stop.
Hot-gas defrost control.

Main characteristic
Direct control of compressor, condenser fans, compressor oil heater, defrosting heaters, evaporator fans, solenoid valve, room light and all  standard-compliant electrical protection devices.
Compact, self-extinguishing ABS housing with  IP65 protection rating and frontal circuit-breaker.
Electronic control with wide LED display and  user-friendly keypad.
System status indicated by icons.
RS485 for connection to TeleNET industrial  supervision network or Modbus-RTU standard  protocol.

 

TECHNICAL CHARACTERISTICS
ECP400
BASE4 VD
ECP750
BASE4 VD
ECP1000
BASE4 VD
Box dimension 350x450x160 mm 350x450x160 mm 350x450x160 mm
Weight 6 Kg 6 Kg 7 Kg
Protection rating IP 65 IP 65 IP 65
Power supply 400 V AC ±10%
50/60 Hz
400 V AC ±10%
50/60 Hz
400 V AC ±10%
50/60 Hz
Load type Three-phase Three-phase Three-phase
Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
Storage temperature
-10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
Relative ambient humidity < 90% Rh
< 90% Rh < 90% Rh
Range of reading -45 ÷ +45°C -45 ÷ +45°C -45 ÷ +45°C
Main switch 32 A 32 A 32 A
Overload protection Thermal relay Thermal relay Thermal relay
General protection Fuses Fuses Fuses
Control PEGO PEGO PEGO
Defrosting Electrical Electrical Electrical
Insulation transformer PRESENT PRESENT PRESENT
Status indicators Led + Display Led + Display Led + Display
Alarm signals Led + Buzzer Led + Buzzer Led + Buzzer
INPUT
Ambient probe NTC 10 KΩ NTC 10 KΩ NTC 10 KΩ
Evaporator probe NTC 10 KΩ NTC 10 KΩ NTC 10 KΩ
Door switch PRESENT PRESENT PRESENT
Oil differential pressure switch
PRESENT
High/low pressure switch PRESENT PRESENT PRESENT
KRIWAN® connection
PRESENT PRESENT PRESENT
OUTPUTS
Compressor 2200 ÷ 3000 W
(3÷4 HP)
3000 ÷ 5500 W
(4÷7,5 HP)
5500 ÷ 7500 W
(7÷10 HP)
Condenser fans output 1 800 W (1 PH)
totals (1 PH)

800 W (1 PH)
totals  (1 PH)

2000 W
(1 PH / 3 PH)
Condenser fans output 2 (separated)
2000 W
(1 PH / 3 PH)
Evaporator fans 2000 W (1 PH) 2000 W (1 PH) 2000 W
(1 PH / 3 PH)
Defrosting heater 7500 W (AC1) 9000 W (AC1) 12000 W (AC1)
Room light PRESENT PRESENT PRESENT
Solenoid valve PRESENT PRESENT PRESENT
Compressor oil heater PRESENT PRESENT PRESENT
Alarm relay PRESENT
(on request)
PRESENT
(on request)
PRESENT
(on request)
Supervision system TELENET / MODBUS-RTU
TELENET / MODBUS-RTU TELENET / MODBUS-RTU
DIMENSION
ECP400-Base4-VD ECP750-Base4-VD ECP1000-Base4-VD
CONNECTION SCHEME
ECP400-Base4-VD ECP750-Base4-VD ECP1000-Base4-VD

 

DOWNLOAD INSTRUCTION
Instruction manual
(documentation available through registration)