ECP 200 EXPERT PULSE
Brochure download

CONTROL PANEL FOR PULSE ELECTRONIC EXPANSION VALVE

Electrical panel for cold room control with  differential magnetothermic circuit breaker and with integrated command of pulse electronic expansion valve 230Vac On/Off and single-phase compressor up to 2HP. This panel can be used also only for the control of the evaporating unit.

 

Applications
Complete control of single-phase static or ventilated refrigeration systems up to 2 HP, with off-cycle or electrical defrosting and direct or pump-down compressor stop.
Thought for systems with evaporator managed by ON/OFF electronic expansion valve at 230 Vac.
Utility for managing the single-phase evaporating unit with electronic expansion valve only ON/OFF at 230 Vac.

Main characteristics
Defrost with real time clock.
Indipendent and separated functions for alarm relay and TeleNET or Modbus-RTU standard protocol.
Control of electronic expansion valve ON/OFF with 230 VAC coil.
The integration of the valve control permits its programming and a simplified management with the same display, enabling an immediate start-up of the system.
Direct control of compressor, defrosting heaters, evaporator fans and room light with free-voltage outputs.
Built-in differential magnetothermic breaker for protection and cut-off of refrigeration unit.
Innovative, stylish design. Transparent cover for access to magnetothermic breaker, all with IP 65 protection rating.
Auxiliary relay with parameter-configured activation (alarm, temperature set-point, direct control via frontal pushbutton, thermostat-holder demisting element).
RS485 for connection to TeleNET industrial supervision network or Modbus-RTU standard protocol.
Easy installation and opening thanks to new hinged cover.
Simple, flexible programming gives extreme versatility of use.
Compressor can be run in pump-down stop mode.
Installation times and costs reduced thanks to incorporation of control and protection in a single room-dedicated unit.

 

TECHNICAL CHARACTERISTICS
ECP 200 EXPERT PULSE
Dimension
262 x 168 x 97 mm
Weigh 2 Kg
Protection rating
IP 65
Power supply
230 VAC ±10% 50/60 Hz
Load type
Single phase
Working temperature
-5 ÷ +50°C
Storage temperature -10 ÷ +70°C
Relative ambient humidity
<90% Rh
Main switch - general protection
2 poles differential magnetothermic 16A
Control
PEGO
Defrosting
Electrical
Component status indicator
Led + Display
Alarm signals
Led + Buzzer
Defrost
PRESENT (RTC)
INPUTS
Ambient probe
NTC 10 KΩ
Evaporator probe
NTC 10 KΩ
Suction probe
NTC 10 KΩ
Evaporation pressure probe
4-20MA / 0-5V RATIO
Door switch
PRESENT
High/low pressure switch
PRESENT
Man in cold room alarm
PRESENT
Compressor work mode selection
Pump down - Thermostat
Outputs
Compressor 1500 W (AC3)
Evaporator fans
500 W (AC3) free voltage contact
Defrosting heater
3000 W (AC1) free voltage contact
Electronic valve
Pulse 230 Vac
Room light
800 W (AC1) free voltage contact
Auxiliary relay or alarm
100 W free voltage contact
Supervision system
TELENET/MODBUS-RTU
DIMENSION
ECP200-EXPERT-PULSE
CONNECTION SCHEME

ECP200-EXPERT-PULSE

(*) = Configurable function

 

DOWNLOAD INSTRUCTION
Instruction manual
(documentation available through registration)