ECP1500/2000/2500 VD CR
Brochure download

A LINE OF POWER AND CONTROL PANELS FOR REFRIGERATION SYSTEMS

A line of power and control panels for refrigeration systems with three-phase compressor up to 25HP to be linked with an out-of-room control unit (i.e. ECP200 Base4 or SLIM Base4). Controls and powers the compressor, condenser fans, evaporator fans, solenoid valve, defrost elements managed by means of cold, fans and defrost call enabling from out-of-room control unit.

Applications
Control of three-phase ventilated refrigeration systems up to 25 HP, with electrical defrost linked to an out-of-room control unit.

Main characteristics
Direct control of compressor, condenser fans, compressor oil element, defrost elements, evaporator fans, solenoid valve and all standard- compliant electrical safeguards.
Compact unit with self-extinguishing ABS housing panel and IP65 protection rating plus circuit breaker on front of panel.
System status indicated by LED icon.
Alarm signal by voltage-free contact.
Can be controlled by thermostat, thermo-regulator or out-of-room control unit.

Options
Compressor shutdown in pump-down mode.
Datalogger function with external control panel Plus 200 Expert CR for temperatures and alarms recording.

 

TECHNICAL CHARACTERISTICS
ECP1500 VD CR
ECP2000 VD CR
ECP2500 VD CR
Box dimension
470x650x210 mm
470x650x210 mm 470x650x210 mm
Weight 20 Kg 20 Kg 20 Kg
Protection rating
IP 65
IP 65 IP 65
Power supply (3F+N+T)
400 V AC ±10%
50/60 Hz
400 V AC ±10%
50/60 Hz
400 V AC ±10%
50/60 Hz
Load type
Three-phase Three-phase Three-phase
Working temperature
-5 ÷ +50°C
-5 ÷ +50°C -5 ÷ +50°C
Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
Relative ambient humidity
< 90% Rh
< 90% Rh
< 90% Rh
Main switch
63 A
63 A 100 A
Overload protection
Motor circuit breaker
Motor circuit breaker Motor circuit breaker
General protection Fuses Fuses Fuses
Control compressor
Control defrost
Control fans
External ON/OFF
External ON/OFF
External ON/OFF
External ON/OFF
External ON/OFF
External ON/OFF
External ON/OFF
External ON/OFF
External ON/OFF
Defrosting
Electrical Electrical Electrical
Insulation transformer
PRESENT PRESENT PRESENT
Status indicators
Led Led Led
Alarm signals
Led Led Led
INPUTS
Compressor
Enable only
Enable only Enable only
Defrosting
Enable only Enable only Enable only
Evaporator fans
Enable only Enable only Enable only
Oil differential pressure switch
PRESENT PRESENT PRESENT
High/low pressure switch PRESENT
PRESENT PRESENT
KRIWAN® connection
PRESENT PRESENT PRESENT
Condenser fans regulator press. switch (r.p.s.)
PRESENT PRESENT PRESENT
Klixon connection for condenser/evaporator fans
PRESENT PRESENT PRESENT
OUTPUTS
Compressor
7500 ÷ 11250 W
(10÷15 HP)
11250 ÷ 15000 W
(15÷20 HP)
15000 ÷ 18750 W
(20÷25 HP)
Condenser fans (separated)
2x2000 W
(1 PH / 3 PH)
2x2000 W
(1 PH / 3 PH)
2x2000 W
(1 PH / 3 PH)
Evaporator fans 2x2000 W
(3 PH)
3x2000 W
(3 PH)
3x2000 W
(3 PH)
Defrosting heaters
15000 W (AC1) 20000 W (AC1) 25000 W (AC1)
Solenoid valve
PRESENT PRESENT PRESENT
Compressor oil heater
PRESENT PRESENT PRESENT
Alarm relay
PRESENT PRESENT PRESENT
DIMENSION
ECP1500-VD-CR ECP2000-VD-CR ECP2500-VD-CR
CONNECTION SCHEME
ECP1500-VD-CR ECP2000-VD-CR ECP2500-VD-CR