PLUS100 2PLT
Brochure download

ELECTRONIC CONTROLLER FOR DOUBLE SYSTEM MANAGEMENT

Electronic controller for double system management. Can manage up to two compressors and two evaporators, operating in call rotation mode (for even utilization) or with a double set-point.
Defrosts can be executed in real time clock mode.
Version with 100Master and remote telephone lead-connected keyboard/display.

 

Applications
Low temperature rooms with double safety system.
Room with single motor condenser unit and double evaporator.

Main characteristics
Single set-point with 2-system control and delayed start of second system, compressor rotation.
Double set-point for gradual application of refrigeration power.
Real time clock defrosts with one or two evaporators, each with end-of-defrost sensor.
Display of ambient temperature, evaporator temperature, systems status.
The Plus200 2PLT electronic controller allows complete control of all the units on a double-system refrigeration plant.
Control of up to two compressors, double evaporator (fans and defrost elements) and room light.
Double evaporator control occurs separately with double end-of-defrost sensor.
Safety devices for the two systems are separate and room light can be controlled by door switch.
Alarm relay fitted as standard.

 

TECHNICAL CHARACTERISTICS
PLUS100 2PLT
Dimension MASTER: 175x121,5x71 mm — PLUS100 2PLT: 203x193x79 mm
Weight 1 Kg
Protection rating IP 65 (keyboard/diplay)
Power supply 230 V AC ±10% 50/60 Hz
Load type Single-phase
Working temperature -5 ÷ +50°C
Storage temperature -10 ÷ +70°C
Relative ambient humidity < 90% Rh
Range of reading -45 ÷ +45°C
Defrosting
Electrical
Status indicators
Display LCD (with backlight)
Alarm signals Display + Buzzer
INPUTS
Ambient probe NTC 10 KΩ
Evaporator probe 1
NTC 10 KΩ
Evaporator probe 2 NTC 10 KΩ
Compressor protection 1
PRESENT
Compressor protection 2 PRESENT
Man in cold-room alarm PRESENT
Door switch PRESENT
OUTPUTS
Compressor 1
1500 W (2 HP)
Compressor 2 750 W (1 HP)
Defrost 1
1500 W (AC1)
Defrost 2 1500 W (AC1)
Evaporator fans 1 500 W
Evaporator fans 2
500 W
Room light
800 W (AC1)
Alarm relay / AUX
(voltage free contact)
PRESENT
Supervision system TELENET
DIMENSION
PLUS100-2PLT
CONNECTION SCHEME
PLUS100-2PLT

 

DOWNLOAD INSTRUCTION
Instruction manual