ECP 200 EXPERT Brochure download

CONTROL PANEL FOR COLD ROOMS

Control panel for cold rooms with single-phase compressor up to 2  HP, specially designed to provide  safety, protection, control and easy-installation – all  in one unit. It allows a complete control of all the components on  a refrigeration system.

Applications
Complete control of single-phase static or  ventilated refrigeration systems up to 2 HP, with off-cycle or electrical defrosting and direct or  pump-down compressor stop.
Control of evaporating unit only with freon  solenoid or remote motor condenser enabling.

Main characteristics
Direct control of compressor, defrosting heaters,  evaporator fans and room light with live outputs  directly connectable to the various devices or free  voltage contacts for control of condensing unit   with its own electrical panel.
Built-in differential magnetothermic breaker for  protection and cut-off of refrigeration unit.
Innovative, stylish design. Transparent cover for  access to magnetothermic breaker, all with  IP 65  protection rating.
Auxiliary relay with parameter-configured  activation (alarm, temperature set-point, direct  control via frontal pushbutton, door heater  elements, remote motor condenser unit  enabling, freon solenoid control enabling where  compressor pump-down operation is applied).
RS485 for connection to TeleNET industrial  supervision network or Modbus-RTU standard  protocol.
Easy installation and opening thanks to new  hinged cover.

 

TECHNICAL CHARACTERISTICSL A
ECP 200 EXPERT
ECP 200 EXPERT BASE 4A
Dimension
262 x 168 x 97 mm
262 x 168 x 97 mm
Weight 0,6 Kg 0,6 Kg
POWER SUPPLY
Voltage 230 VAC ±10% 50/60 Hz
230 VAC ±10% 50/60 Hz
Max absorbed power
7 VA
7 VA

AMBIENT CONDITIONS
Working temperature
-5 ÷ +50°C
-5 ÷ +50°C
Storage temperature
-30 ÷ +70°C -30 ÷ +70°C
Relative humidity
<90% Rh
<90% Rh
GENERAL CHARACTERISTICS
Connectable sensor types
NTC 10 KΩ
NTC 10 KΩ
Resolution 0,1 °C
0,1 °C
Probe read precision
± 0,5 °C ± 0,5 °C
Read range
-45 ÷ +45°C -45 ÷ +45°C
OUTPUTS CHARACTERISTICS
Compressor 1500 W (2HP)
1500 W (2HP)
free voltage contact
Defrost 3000 W (AC1)
3000 W (AC1)
free voltage contact
Fans 500 W (AC3)
500 W (AC3)
free voltage contact
Room light
800 W (AC1)
800 W (AC1)
free voltage contact
Configurable alarm contact / AUX
PRESENT PRESENT
Supervision system
TELENET/MODBUS-RTU TELENET/MODBUS-RTU
GENERAL ELECTRIC PROTECTION
Bipolar differential magnetothermic circuit breaker
16A ID= 300 mA
Switching power 4,5 kA
ID=30 mA (on request)
16A ID= 300 mA
Switching power 4,5 kA
ID=30 mA (on request)
INSULATION AND MECHANICAL CHARACTERISTICS
Box protection rating
IP 65
IP 65
Box material
Self-extinguishing ABS
Self-extinguishing ABS
Insulation type
Class II
Class II
DIMENSION
ECP200-EXPERT ECP200-EXPERT-base-4A
CONNECTION SCHEME

ECP200-EXPERT ECP200-EXPERT-base-4A

(*) = Configurable function
(*) = Configurable function

 

DOWNLOAD INSTRUCTION
Instruction manual
(documentation available through registration)