A LINE OF POWER AND CONTROL BOARDS FOR REFRIGERATION SYSTEM

A line of power and control boards for refrigeration systems with three-phase compressors up to 10 HP that provide complete cold room management. Cold room light and system stand-by switches incorporated on front of panel. Integrated thermo-regulator controls compressor, ventilation and defrosting. The unit also controls the door switch, which automatically turns on the room light, and compressor and fan shutdown.

ECP 400-1000 VD T

Applications
Complete control of three-phase static or ventilated refrigeration systems up to 10 HP, with electric or off-cycle defrost.

Main characteristic
Direct control of compressor, condenser fans, compressor oil element, defrost elements, evaporator fans, solenoid valve, room light and all standard-compliant electrical safeguards.
Compact unit with self-extinguishing ABS housing panel and IP55 protection rating plus circuit breaker on front of panel.
Integrated thermo-regulator: various models available.
System status indicated by LED icon.
Room light and system stand-by switches on front of panel.

Options
Installation of magnetothermic circuit breakers instead of fuses.
Compressor shutdown in pump-down mode.
Hot gas defrost control.
Wide range of thermo-regulator models available.
VS version (ventilated/static, pause/ventilated defrost).



 

TECHNICAL CHARACTERISTICS
ECP400 VD T
ECP750 VD T
ECP1000 VD T
Box dimension 350x450x160 mm 350x450x160 mm 350x450x160 mm
Weight 6 Kg 6 Kg 7 Kg
Protection rating
IP 55 IP 55 IP 55
Power supply (3F+N+T)
400 V AC ±10%
50/60 Hz
400 V AC ±10%
50/60 Hz
400 V AC ±10%
50/60 Hz
Load type Three-phase Three-phase Three-phase
Working temperature -5 ÷ +50°C -5 ÷ +50°C -5 ÷ +50°C
Storage temperature -10 ÷ +70°C -10 ÷ +70°C -10 ÷ +70°C
Relative ambient humidity
< 90% Rh
< 90% Rh < 90% Rh
Main switch
32 A 32 A 32 A
Overload protection Thermal relay
Thermal relay Thermal relay
General protection Fuses Fuses Fuses
Control
Thermoregulator Thermoregulator Thermoregulator
Defrosting
Electrical Electrical Electrical
Insulation transformer
PRESENT PRESENT PRESENT
Status indicators
Led + Display Led + Display Led + Display
Alarm signals
Led Led Led
INPUTS
Ambient probe
NTC NTC NTC
Evaporatoe probe
NTC NTC NTC
Door switch
PRESENT PRESENT PRESENT
Oil differential pressure switch
PRESENT
High/low pressure switch
PRESENT PRESENT PRESENT
KRIWAN® connection
PRESENT PRESENT PRESENT
Condenser fans regulator press. switch (r.p.s)
PRESENT PRESENT PRESENT
OUTPUT
Compressor
2200 ÷ 3000 W
(3÷4 HP)
3000 ÷ 5500 W
(4÷7,5 HP)
5500 ÷ 7500 W
(7÷10 HP)
Condenser fans output 1
800 W------(1 PH) 800 W------(1 PH)
2000 W
(1 PH / 3 PH)
Condenser fans output 2
total -------(1 PH) total -------(1 PH) 2000 W
(1 PH / 3 PH)
Evaporator fans 2000 W (1 PH) 2000 W (1 PH) 2000 W
(1 PH / 3 PH)
Defrosting heaters
7500 W (AC1) 9000 W (AC1) 12000 W (AC1)
Room light
PRESENT PRESENT PRESENT
Solenoid valve
PRESENT PRESENT PRESENT
Compressor oil heater
PRESENT PRESENT PRESENT
DIMENSION
ECP400-VD-T ECP750-VD-T ECP1000-VD-T
CONNECTION SCHEME
ECP400-VD-T ECP750-VD-T ECP1000-VD-T