CONTROL BOARD FOR COLD ROOMS WITH DATALOGGER FUNCTION

Control board for complete control of cold rooms with three-phase compressor up to 7,5 HP and Datalogger function. A large backlit LCD allows for simultaneous display of ambient temperature, evaporator temperature, calendar and all other refrigeration system information. The temperature recorder is independent from the controller used to manage the refrigeration system and can record (for up to  year) ambient temperature and relative alarms through an electronic circuit equipped with autonomous power and temperature sensor (as per EN 12830). The recorder can be removed or replaced without any interruption to normal cold room operation. Moreover, defrosts can be carried out in real time clock mode and it is possible to connect up to the TeleNET supervision system. Magnetothermic protection and motor circuit breaker for the compressor accessible from the front panel linked to an innovative form makes it a perfect and functional choice.

PLUS 300 EXPERT VD

Applications
Control of three-phase refrigeration plant up to 7.5 HP , static or ventilated, with off-cycle or electrical defrosting.

Options
SD (Secure Digital™) memory for transfer of temperature recordings onto personal computer.
RS version with thermostat door heater and discharge heater.

Main characteristics
Direct control of the compressor, condenser fans, compressor oil heater, defrosting heaters, evaporator fans, solenoid valve, room light and all standard-compliant electrical safeguards.
General magnetothermic circuit breaker accessible from the front panel, which cuts the general power supply.
Adjustable motor circuit breaker for compressor protection accessible from the front panel.
Easy wiring on the internal terminal block.
Selection of functioning mode for the compressor (pump-down / thermostat).
Auxiliary relay with activation configurable by parameter.
Transparent cover for access to magnetothermic circuit breaker, all with Ip65 protection rating.
Control electronics with large backlit LCD and user-friendly keypad.
Simultaneous display on LCD of ambient temperature, evaporator temperature, calendar and system status.
Recording of ambient temperature and relative alarms (up to 1 year) with recorder independent from cold room system control.
Secure Digital™ slot built into controller for data downloads.
Defrosts can be carried out in real time clock mode.
RS485 for connection to TeleNET industrial supervision network.
TeleNET SD software to download data on personal computer (provided free of charge with product).

 

TECHNICAL CHARACTERISTICS
PLUS 300 EXPERT VD 4
PLUS 300 EXPERT VD 7
Box dimension
400 x 300 x 135 mm
400 x 300 x 135 mm
Weight
9 Kg
10 Kg
Protection rating
IP 65
IP 65
Power supply (3F + N + T)
400 V AC ±10% 50/60 Hz
400 V AC ±10% 50/60 Hz
Load type
Three-phase Three-phase
Working temperature
-5 ÷ +40°C
-5 ÷ +40°C
Storage temperature -25 ÷ +55°C -25 ÷ +55°C
Relative ambient humidity
30% - 90% Rh
without condensate
30% - 90% Rh
without condensate
Main switch - general protection
4 poles magnetothermic 16A
4 poles magnetothermic 25A
Compressor protection
Motor circuit breaker
Motor circuit breaker
Control
PEGO PEGO
Defrosting
Electrical Electrical
Status indicator
Display LCD (with backlight) Display LCD (with backlight)
Alarm signals
Display LCD + Buzzer
Display LCD + Buzzer
INPUT
Ambient probe
NTC 10K Ω
NTC 10K Ω
Evaporator probe
NTC 10K Ω NTC 10K Ω
Datalogger probe
NTC 10K Ω NTC 10K Ω
Door switch
PRESENT PRESENT
High/low pressure switch
PRESENT PRESENT
KRIWAN® connection
PRESENT PRESENT
Compressor functioning mode selection
Pump-Down / Thermostat
Pump-Down / Thermostat
OUTPUT
Compressor
370 W ÷ 3000 W (0,5 ÷ 4 HP)
3000 W ÷ 5500 W (4 ÷ 7,5 HP)
Condenser fans output 1
800 W (1PH)
800 W   (1PH)
TOTAL   (1PH)
Condenser fans output 2 (separated)

Evaporator fans
500 W (1PH) 2000 W (1PH / 3PH)
Defrosting heaters
6000 W (AC1)
Eq. resistive load

9000 W (AC1)
Eq. resistive load
Room light
800 W (AC1) - Resistive load 800 W (AC1) - Resistive load
Solenoid valve
PRESENT PRESENT
Compressor oil heater
PRESENT PRESENT
Alarm relay
PRESENT PRESENT
Supervision system
TELENET TELENET
DATALOGGER
Datalogger Independent circuit
Independent circuit
Max. number of readings without overwrite
1 year (cyclic memory)
1 year (cyclic memory)
DESIGNATION
Standard reference
EN 12830
EN 12830
Suitability S (storage)
S (storage)
Location
A A
Accuracy class
1 1
DIMENSION
PLUS300-EXPERT-VD-4 ECP300-EXPERT-VD-7
CONNECTION SCHEME
PLUS300-EXPERT-VD-4 PLUS300-EXPERT-VD-7

 

DOWNLOAD INSTRUCTION
Instruction manual