PLUS200 EXPERT - DATALOGGER
Brochure download

CONTROL BOARD FOR COLD ROOMS WITH DATALOGGER FUNCTION

Control board for complete control of cold rooms with single-phase compressor up to 2 HP and Datalogger function. A large backlit LCD allows for simultaneous display of ambient temperature, evaporator temperature, calendar and all other refrigeration system information. The temperature recorder is independent from the controller used to manage the refrigeration system and can record (for up to 1 year) ambient temperature and relative alarms through an electronic circuit equipped with autonomous power and temperature sensor (as per EN 12830). The recorder can be removed or replaced without any interruption to normal cold room operation. Moreover, defrosts can be carried out in real time clock mode and it is possible to connect up to the TeleNET supervision system.

PLUS 200 EXPERT

Applications
Complete control of single-phase static or ventilated systems up to 2 HP , off-cycle or electrical defrost, direct or pump-down mode compressor stop together with Datalogger function.
Control of single-phase evaporating unit only with freon solenoid enabling or remote motor condenser enabling, together with Datalogger function.

Options
SD (Secure Digital™) memory for transfer of temperature recordings onto personal computer.
CR version with free-voltage contacts to remotely control a power panel.

Main characteristics
Direct control of compressor, defrost heaters, evaporator fans, room light with 230Vac contacts directly connectable to various devices.
Control electronics with large backlit LCD and user-friendly keypad.
Simultaneous display on LCD of ambient temperature, evaporator temperature, calendar and system status.
Recording of ambient temperature and relative alarms (up to 1 year) with recorder independent from cold room system control.
Secure Digital™ slot built into controller for data downloads.
Defrosts can be carried out in real time clock mode.
RS485 for connection to TeleNET industrial supervision network.
Safety and protection guaranteed and certified thanks to incorporated differential magnotothermic circuit breaker, which cuts the power supply.
Easy installation and opening thanks to new hinged cover.
Auxiliary relay with parameter-configurable activation.
Registration probe with calibration certificate included.
TeleNET SD software to download data on personal computer (provided free of charge with product).

 

TECHNICAL CHARACTERISTICS
PLUS 200 EXPERT
PLUS 200 EXPERT CR
Dimension 262x168x97 mm 262x168x97 mm
Weight
1 Kg 1 Kg
POWER SUPPLY
Voltage 230 V AC ±10% 50/60 Hz 230 V AC ±10% 50/60 Hz
Max absorbed power
-7 VA -7 VA

AMBIENT CONDITIONS
Working temperature
0 ÷ +50°C 0 ÷ +50°C
Storage temperature -20 ÷ +60°C -20 ÷ +60°C
Relative ambient humidity
<90% Rh <90% Rh
GENERAL CHARACTERISTICS
Connectable sensor types
NTC 10 KΩ NTC 10 KΩ
Resolution 0,1 °C 0,1 °C
Range of reading
-45 ÷ +45°C -45 ÷ +45°C
RECORDING CHARACTERISTICS
Maximum number of readings without overwrite
1 year (cyclic memory) 1 year (cyclic memory)
OUTPUT CHARACTERISTICS
Compressor 1500 W (AC3) 1500 W (AC3)
free voltage contact
Defrost 3000 W (AC1) 3000 W (AC1)
free voltage contact
Fans 500 W (AC3) 500 W (AC3)
free voltage contact
Room light
800 W (AC1) 800 W (AC1)
free voltage contact
Configurable alarm contact
(voltage-free contact)
PRESENT PRESENT
Supervision system
TELENET TELENET
GENERAL ELECTRIC PROTECTION
Bipolar differential magnetothermic circuit breaker
16A ID= 300 mA
Switching power  4,5 kA
ID=30 mA (on request)

INSULATION AND MECHANICAL CHARACTERISTICS
Box protection rating
IP 65 IP 65
Box material
Self-extinguishing ABS
Self-extinguishing ABS
Type of insulation
Class II Class II
DESIGNATION
Standard reference
EN 12830 EN 12830
Suitability S (storage) S (storage)
Location
A A
Accuracy class
1 1
DIMENSION
PLUS200-EXPERT PLUS200-EXPERT-CR
CONNECTION SCHEME

PLUS200-EXPERT

PLUS200-EXPERT-CR

(*) = Configurable function
(*) = Configurable function

 

DOWNLOAD INSTRUCTION
Instruction manual
(documentation available through registration)